Menu Close

TFV 600 Ex Radial Fan

The high pressure centrifugal fans in the TFV series are well-equipped for such tasks: They transport up to 16,000 m³/h of air, even over longer distances and with back pressure, and because they are extremely robust they are able to handle harsh working environments.

TFV 600 Ex Radial Fan
Centrifugal fan TFV 600 Ex

Versatile high-pressure fan for long air conveying distances in Ex protection zones

Proper ventilation is not only important for a pleasant working environment, but is also essential in many areas for reasons of occupational safety and due to official requirements.

Enquire Now

Free standard delivery over £200

Enquire Now

Centrifugal fan TFV 600 Ex

Versatile high-pressure fan for long air conveying distances in Ex protection zones

Proper ventilation is not only important for a pleasant working environment, but is also essential in many areas for reasons of occupational safety and due to official requirements.

The ventilation of rooms removes harmful substances such as paint or varnish fumes, welding smoke, dust particles, carbon monoxide, nitrogen oxide, carbon dioxide and water vapour.

The TFV 600 Ex is designed for a large conveying capacity in Ex-protected areas with high counter pressure, even with long transport routes via several interconnected air transport hoses.

This makes the TFV 600 Ex the ideal conveyor fan for ventilation in Ex-protection zones of class 2, for example for tank cleaning, in port facilities, refineries, shafts or silos.

Even with long hose distances of 50 meters with several bends, this powerful radial fan guarantees a high volume of air, because in contrast to axial fans, the TFV 600 Ex conveys the air perpendicular to the impeller axis according to the principle of a centrifuge, in which the air is pressed outwards and in a helical shape Housing is compacted.

And because the centrifugal fan, which is designed in accordance with ATEX directive 2014/34 / EU, is integrated into a robust, powder-coated steel housing with a highly resistant two-component paint finish of this quality device, which is completely made in Germany, it does not mind its use in aggressive environments. The housing is optionally available in all the required types of steel.

In addition to the frameless standard version, the TFV 600 Ex is optionally also available as shown, including an additional frame made of galvanized steel with robust transport rollers, forklift slots and crane lifting corners. The transport frame not only offers you maximum mobility for use in frequently changing locations, but can also be stacked twice to save space during transport or storage.

The switches, cables and plugs of the TFV 600 Ex are approved for use where there is a risk of explosion. Suitable coupling plugs that are approved for use in zones 1, 2, 21 and 22 can be supplied for connection extensions.

A star-delta contactor combination 18.5 kW for EX zone 22, 400 V, AC3, IP 55 is also optionally available for the TFV 600 Ex.

Here are some practical advantages of the TFV 600 at a glance:

  • Development, design, production: 100% Trotec
  • Explosion protection group II, category 3G, temperature class 4
  • Robust quality unit “made in Germany” with high conveying capacity
  • Splash-proof design (IP55)
  • Fan motor is outside the main airflow
  • Can be connected to both suction and discharge ducts
  • Stable characteristic ranges and continuously high pressure
  • Also available for explosion protection group II, category 2G (zone 1), category 2D (zone 21) and category 3D (zone 2)

Explosion protection is the protection against the formation of explosions and their effects. It serves to prevent damage caused by systems, technical products, etc. Explosion protection includes legal provisions such as the ATEX directives of the European Union. Important: Please inform yourself about the use of explosion-proof fans from our service staff!

The frame on request

Technical

General information
Article number1.510.002.042
Air flow rate
Air volume Level Max. – Freely blowing [m³/h]16,000
Air volume at air pressure
m³/h10,000
Pa4,000
Air current
Blowing outStandard
Sucking inStandard
Air discharge velocity
Air discharge speed [m/s]21
Air discharge speed [km/h]75.6
Fan
stages1
Air pressure
Level Max. [Pa]4,900
Transport medium temperature
max. [°C]80
Ambient conditions
Min. temperature range [°C]-20
Max. temperature range [°C]40
Safety feature
IP type of protection55
Electrical values
Mains connection400 V, 50 Hz
Power input [kW]18.5
Recommended fusing [A]32
Nominal current consumption [A]32
Electric connection
Connection plugCEE 63 A
Provided by the customerStandard
Cable length [m]Not Available
Hose connection
Suction nozzle [mm]600
Exhaust connection [mm]450
Sound values
Distance 1 m [dB(A)]84
Distance 3 m [dB(A)]78
Explosion protection
Zone2
Protection classII 3G, T4
Dimensions
Length (packaging excluded) [mm]1,305
Width (packaging excluded) [mm]1,250
Height (packaging excluded) [mm]1,170
Weight
(packaging excluded) [kg]233