Menu Close

Radial Fan TFV 900 Ex

Proper ventilation is not only important for a pleasant working environment, but is also mandatory in many areas for occupational safety reasons alone and due to official regulations.

The ventilation of rooms removes harmful substances such as paint or varnish fumes, welding fumes, dust particles, carbon monoxide, nitrogen oxide, carbon dioxide and water vapor.

Whether large-volume ventilation of duct and pipe systems in Class 2 explosion protection zones, tank cleaning of cargo ships or construction work in refinery areas – the TFV 900 EX high-pressure centrifugal fan, designed in accordance with ATEX Directive 2014/34/EU, is ideally equipped for such tasks because it conveys up to 25,000 m³/h of air even through connected air transport hoses on very long conveying distances with high back pressures and is designed to be extremely stable for harsh practical environments.

Enquire Now

Free standard delivery over £200

Enquire Now

Proper ventilation is not only important for a pleasant working environment, but is also mandatory in many areas for occupational safety reasons alone and due to official regulations.

The ventilation of rooms removes harmful substances such as paint or varnish fumes, welding fumes, dust particles, carbon monoxide, nitrogen oxide, carbon dioxide and water vapor.

Whether large-volume ventilation of duct and pipe systems in Class 2 explosion protection zones, tank cleaning of cargo ships or construction work in refinery areas – the TFV 900 EX high-pressure centrifugal fan, designed in accordance with ATEX Directive 2014/34/EU, is ideally equipped for such tasks because it conveys up to 25,000 m³/h of air even through connected air transport hoses on very long conveying distances with high back pressures and is designed to be extremely stable for harsh practical environments.

Aggressive environments do not affect this quality unit, as the centrifugal fan is integrated into a robust, powder-coated steel housing with a highly resistant two-component paint finish. All desired steel grades are optionally available.

In addition to the frameless standard version, the TFV 900 Ex is also available on request as shown including an additional frame made of galvanized steel with robust transport rollers, forklift slots and crane lifting corners. The transport frame offers you maximum mobility and is ideally suited for use at frequently changing locations.

Switches, cables and plugs of the TFV 900 Ex are approved for use under explosion hazard. Suitable coupling plugs can be supplied for connection extensions, which are approved for use in zones 1, 2, 21 and 22.

Also optionally available for the TFV 900 Ex is a star-delta contactor combination 18.5 kW for EX zone 22, 400 V, AC3, IP 55.

Here are some practical advantages of the TFV 900 Ex at a glance:

  • Development, design, manufacturing: 100 % Trotec
  • Ex-protection group II, category 3G, temperature class 4
  • Robust quality unit “made in Germany” with high conveying capacity
  • Splash-proof design (IP55)
  • Fan motor is located outside the main air stream
  • Can be connected to both intake and exhaust ducts
  • Stable characteristic curve ranges and continuous high pressure
  • Optionally available for explosion protection group II, category 2G (zone 1), category 2D (zone 21) and category 3D (zone 2)

Explosion protection is the protection against the occurrence of explosions and their effects. It is used to prevent damage caused by equipment, technical products, etc. Explosion protection includes legal regulations such as the ATEX directives of the European Union. Important: Please contact our service staff for information on the use of explosion-proof fans!

The picture shows the TFV 900 Ex installed in a frame. This is not included in the scope of delivery and is available on request!

Technical

General information
Article number1.510.002.052
Air flow rate
Air volume Level Max. – Freely blowing [m³/h]33,600
Air volume at air pressure
m³/h25,000
Pa1,900
Air current
Blowing outStandard
Sucking inStandard
Air discharge velocity
Air discharge speed [m/s]34
Air discharge speed [km/h]122.4
Fan
stages1
Air pressure
Level Max. [Pa]2,150
Transport medium temperature
max. [°C]60
Ambient conditions
Min. temperature range [°C]-20
Max. temperature range [°C]40
Safety feature
IP type of protection55
Electrical values
Mains connection400 V, 50 Hz
Power input [kW]18.5
Recommended fusing [A]63
Nominal current consumption [A]36
Electric connection
Connection plugCEE 63 A
Provided by the customerStandard
Cable length [m]Not Available
Hose connection
Suction nozzle [mm]630
Exhaust connection [mm]630
Sound values
Distance 1 m [dB(A)]82
Distance 3 m [dB(A)]76
Explosion protection
Zone2
Protection classII3G, T4
Dimensions
Length (packaging excluded) [mm]1,770
Width (packaging excluded) [mm]1,200
Height (packaging excluded) [mm]1,650
Weight
(packaging excluded) [kg]450